Sample Commissioning Report

This is what "verified" looks like.

Every TruFit™ replacement ends with a signed Commissioning Report: the actual measurements from your system, each one checked against the manufacturer's specification. Here's a sample, so you know exactly what you'll get.

Install day

Installed to the Tru Fit standard

The install crew pressure-tests and evacuates the refrigerant circuit, sets the charge to manufacturer spec, and starts up the system.

→ A few days later
Commissioning visit

Verified by a separate technician

A TruClimate service technician who wasn't on the install crew returns, with the system settled in, to measure, test every safety, and sign the report.

TruFit™ Commissioning Report

Phase 5 of the TruFit™ Replacement System · Quality Control & Commissioning

Sample report. Customer, address, and job details are fictional. Readings are representative of a typical TruFit™ installation.
Customer Jordan & Casey Sample
Service address 1234 Example Creek Dr, Burleson, TX 76028
Job number TF-000000
System System 1 of 1 (whole home)
Installation date October 14, 2026
Commissioning visit October 17, 2026
Install crew lead M. Torres
Commissioning technician D. Alvarez

Every TruFit™ system is commissioned in two steps. Our install crew completes the installation, then a TruClimate service technician returns a few days later, with the system settled in, to measure, test every safety, and sign this report.

01 Installed equipment

The equipment matched to your home's Manual J load calculation.

Component
Brand / series
Model
Serial
Outdoor unit
American Standard Silver Series AC, 3 ton
Model SAMPLE-AC036
Serial SAMPLE-0001
Gas furnace
American Standard 80% two-stage, 60,000 BTU
Model SAMPLE-GF060
Serial SAMPLE-0002
Evaporator coil
American Standard cased coil, 3 ton, TXV
Model SAMPLE-EC036
Serial SAMPLE-0003
Thermostat
Smart thermostat, Wi-Fi
Model SAMPLE-TSTAT
Serial N/A
Refrigerant R-454B (A2L)
Metering device TXV
Line set 25 ft, 3/8" liquid / 3/4" suction
Design airflow 1,200 CFM (400 CFM/ton)

Why it matters: Model and serial numbers are recorded for warranty registration and future service, and the equipment is tied back to the load calculation, not the size of the old unit.

02 Refrigerant circuit integrity

A leak-free, moisture-free refrigerant circuit is the foundation of a long equipment life.

Test / reading
Measured
Specification / target
Result
Standing nitrogen pressure test
Measured 400 psig, 30 min, no drop
Spec / target Hold test pressure with no loss
PASS
Brazing performed under nitrogen purge
Measured Yes
Spec / target Required on all brazed joints
PASS
Deep evacuation (core tools, 3/8" hoses)
Measured 285 microns
Spec / target 300 microns or lower
PASS
Vacuum decay test (isolated 10 min)
Measured Rose to 410, then stable
Spec / target Holds below 500 microns
PASS
Line set charge adjustment
Measured +6 oz weighed in
Spec / target Per manufacturer for line set length
PASS
A2L refrigerant locking caps installed
Measured Yes
Spec / target Installed at commissioning visit
PASS

Why it matters: Leaks and moisture are the top causes of early compressor failure. A deep vacuum that holds proves the system is tight and dry before it ever runs.

03 Refrigerant charge verification

Charge was set to manufacturer specification at install, then verified here by subcooling and superheat under real operating conditions.

Outdoor temp 88°F
Return air 75°F DB / 63°F WB
Supply air 56°F DB
Charge adjustment at QC None required
Test / reading
Measured
Specification / target
Result
Suction pressure / saturation
Measured 122 psig / 45°F
Spec / target Reference for superheat
PASS
Suction line temperature
Measured 54°F
Spec / target Reference for superheat
PASS
Superheat
Measured 9°F
Spec / target TXV system, 8 to 12°F typical
PASS
Liquid pressure / saturation
Measured 335 psig / 106°F
Spec / target Reference for subcooling
PASS
Liquid line temperature
Measured 96°F
Spec / target Reference for subcooling
PASS
Subcooling
Measured 10°F
Spec / target Manufacturer target 10°F (±1°F)
PASS
Cooling temperature split
Measured 19°F
Spec / target Within range for measured conditions
PASS

Why it matters: A system that is even slightly over- or undercharged loses efficiency and capacity, and you can't tell by feel. These readings confirm the charge is right.

04 Airflow

Correct airflow across the coil and furnace delivers comfort, humidity control, and the efficiency your equipment is rated for.

Test / reading
Measured
Specification / target
Result
Blower set to design airflow (cooling / heating)
Measured Tap 4 / Tap 2
Spec / target Mfr blower table, 1,200 CFM design
PASS
Heating temperature rise
Measured 48°F
Spec / target Nameplate range 30 to 60°F
PASS

Why it matters: Most systems ship with factory blower settings that don't match the home. Setting airflow to the design number is what makes the system perform as rated.

05 Electrical

Correct voltage and amp draw confirm the equipment is wired, protected, and running within its design limits.

Test / reading
Measured
Specification / target
Result
Supply voltage at disconnect
Measured 241 V
Spec / target 208/230 V rated, 197 to 253 V
PASS
Compressor amp draw
Measured 10.9 A
Spec / target Below 12.8 A RLA
PASS
Condenser fan motor amp draw
Measured 0.9 A
Spec / target Below 1.1 A FLA
PASS
Indoor blower amp draw
Measured 4.1 A
Spec / target Below nameplate FLA
PASS
Run capacitor (compressor / fan)
Measured 44.6 / 5.0 MFD
Spec / target Rated 45 / 5 MFD, ±6%
PASS
Breaker size vs. nameplate MOCP
Measured 25 A breaker
Spec / target 25 A max overcurrent protection
PASS

Why it matters: Amp draw is a direct read on how hard the motors are working. Readings inside the rated limits mean the equipment isn't being strained from day one.

06 Gas heating and combustion safety

Gas pressure and combustion testing verify safe, complete combustion and proper venting.

Test / reading
Measured
Specification / target
Result
Gas inlet pressure
Measured 7.0 in. w.c.
Spec / target Natural gas, 4.5 to 10.5 in. w.c.
PASS
Manifold pressure (high fire)
Measured 3.5 in. w.c.
Spec / target Manufacturer spec 3.5 in. w.c.
PASS
Carbon monoxide in flue (air-free)
Measured 22 ppm
Spec / target Well below manufacturer limit
PASS
Flame sensor signal
Measured 3.8 µA
Spec / target Stable signal above minimum
PASS
Venting and draft verified
Measured Yes
Spec / target Category I vent, proper rise and clearance
PASS

Why it matters: This is your family's safety. Combustion is measured with an analyzer, not eyeballed, and venting is confirmed to carry exhaust out of the home.

07 Safeties and controls tested

Each safety device was physically tripped to confirm it shuts the system down as designed.

  • Condensate overflow switch
  • A2L leak sensor and mitigation
  • Furnace high limit
  • Flame rollout switches
  • Inducer pressure switch
  • Gas valve low and high fire staging
  • High pressure switch
  • Thermostat: all modes and stages
  • Primary drain trapped and flowing

Why it matters: A safety switch you've never tested is a guess. Each one is tripped on purpose to prove it works before you ever need it.

08 Installation finish items

The details that separate a good install from a Tru Fit ™ install.

  • Line set insulated, UV protected
  • Outdoor unit level, clearances met
  • Disconnect and whip to code
  • Ductwork connections sealed
  • Homeowner walkthrough completed
  • New filter installed (16x25x1)
  • Thermostat programmed
  • Warranty registration submitted
  • Old equipment removed, site clean

Why it matters: These are the details that show up years later as a sweating line set, a clogged drain, or a lapsed warranty. They get checked off, not assumed.

Commissioning result PASS: System
commissioned

Technician notes: All readings within specification. No charge adjustment required. A2L locking caps installed. Homeowner shown filter location and thermostat operation.

D. Alvarez Commissioning technician · 10/17/2026
Jordan Sample Homeowner acknowledgment · 10/17/2026

This system was installed to the TruFit™ Installation Standard, modeled on ANSI/ACCA 5 QI, and verified by a separate TruClimate service technician. Keep this report with your home records; it documents your system's baseline performance for future maintenance and warranty service.

Your system, documented

Want a report like this for your home?

Every TruFit™ replacement includes one. Schedule a home comfort evaluation, or get a preliminary replacement estimate online.